The alarm relay mode of the craft interface panel for both yellow and red alarms.
Both yellow and red alarms could be cut off by a front panel Alarm Cutoff / Lamp Test (ACO/LT) button.
In the pass-on mode, the alarm relay will be activated to pass on the yellow or red alarms. In the cut-off mode, both yellow and red alarms will be cut off from the alarm relays which are normally connected to audible sirens or visual flashing devices.
jnxYellowAlarmState
1.3.6.1.4.1.2636.3.4.2.2.1
INTEGER1 = other2 = off3 = on · Integer32
The yellow alarm state on the craft interface panel.
The yellow alarm is on when there is some system warning such as maintenance alert or significant temperature increase.
This yellow alarm state could be turned off by the ACO/LT (Alarm Cut Off / Lamp Test) button on the front panel module.
jnxYellowAlarmCount
1.3.6.1.4.1.2636.3.4.2.2.2
Gauge32
The number of currently active and non-silent yellow alarms.
This object is independent of the ACO/LT (Alarm Cut Off / Lamp Test) button.
jnxYellowAlarmLastChange
1.3.6.1.4.1.2636.3.4.2.2.3
TimeStampThe value of the sysUpTime object at which a specific occurrence happened. The specific occurrence must be
defined in the description of any object defined using this type.
If sysUpTime is reset to zero as a result of a re- initialization of the network management (sub)system, then the values of all TimeStamp objects are also reset. However, after approximately 497 days without a re- initialization, the sysUpTime object will reach 2^^32-1 and then increment around to zero; in this case, existing values of TimeStamp objects do not change. This can lead to ambiguities in the value of TimeStamp objects. · TimeTicks
The value of sysUpTime when the yellow alarm last changed - either from off to on or vice versa. Zero if unknown or never changed since the agent was up.
jnxRedAlarmState
1.3.6.1.4.1.2636.3.4.2.3.1
INTEGER1 = other2 = off3 = on · Integer32
The red alarm indication on the craft interface panel.
The red alarm is on when there is some system failure or power supply failure or the system is experiencing a hardware malfunction or some threshold is being exceeded.
This red alarm state could be turned off by the ACO/LT (Alarm Cut Off / Lamp Test) button on the front panel module.
jnxRedAlarmCount
1.3.6.1.4.1.2636.3.4.2.3.2
Gauge32
The number of currently active and non-silent red alarms.
This object is independent of the ACO/LT (Alarm Cut Off / Lamp Test) button.
jnxRedAlarmLastChange
1.3.6.1.4.1.2636.3.4.2.3.3
TimeStampThe value of the sysUpTime object at which a specific occurrence happened. The specific occurrence must be
defined in the description of any object defined using this type.
If sysUpTime is reset to zero as a result of a re- initialization of the network management (sub)system, then the values of all TimeStamp objects are also reset. However, after approximately 497 days without a re- initialization, the sysUpTime object will reach 2^^32-1 and then increment around to zero; in this case, existing values of TimeStamp objects do not change. This can lead to ambiguities in the value of TimeStamp objects. · TimeTicks
The value of sysUpTime when the red alarm last changed - either from off to on or vice versa. Zero if unknown or never changed since the agent was up.